H7CX-R11-N

buiding

Type: H7CX-R11-N

Function Tachometer
Preset stages 1stages
Rated supply voltage 100 to 240 VAC 50/60 Hz
Operating voltage range 85% to 110% of the rated power supply voltage
Power consumption Approx. 9.4 VA
External power supply 12 VDC (±10%) 100 mA
Tachometer (Input mode) 1 input
Tachometer (Pulse measurement method) Periodic measurement / Continuous measurement / Continuous measurement
Tachometer (Sampling period) Periodic measurement: 200 ms
Continuous measurement: Continuous (minimum interval of 10 ms)
Continuous measurement: Continuous (minimum interval of 10 ms)
Tachometer (Max. counting speed) Periodic measurement: 30 Hz
Periodic measurement: 10 kHz
Continuous measurement: 
Continuous measurement:
Tachometer (Count range) 0 to 999999
Tachometer (Measuring ranges) Periodic measurement: 0.001 Hz to 30.00 Hz
Periodic measurement: 0.001 Hz to 10 kHz
Continuous measurement: 0.026 to 999999 s
Continuous measurement: 0.003 to 999999 s
Tachometer (Minimum input signal width) Periodic measurement: 
Continuous measurement: 10 ms
Continuous measurement: 1 ms
Tachometer (Measuring accuracy) ±0.1% F.S. ±1 digit max. (at 23 ±5 ℃)
Tachometer (Output modes) Except 2-input individual measurement: Upper and lower limit/ area/ upper limit/ lower limit, 2-input individual measurement: Upper limit/ lower limit
Tachometer (Auto-zero time) 0.1 to 999.9 s
Tachometer (Startup time) 0.0 to 99.9 s
Tachometer (Average processing) OFF/ 2 times/ 4 times/ 8 times
Input signal Count / Hold
Input method No-voltage/Voltage input (selectable)
No-voltage input (No-contact input) Short-circuit (ON) impedance: 1 kΩ
Leakage current (0 Ω): 12 mA
Residual voltage: 3 V max.
Open circuit impedance: 100 kΩ
Maximum voltage: 30 V
No-voltage input (Contact input) Use a contact which can adequately switch 5 mA at 10 V.
Voltage input Hight level: 4.5 to 30 VDC
Low level: 0 to 2 VDC
Input resistance: 4.7 kΩ
Applicable two-wire sensor leakage current: 1.5 mA
Switching capacity: 5 mA
Residual voltage: 3 V
Operating voltage: 10 VDC
Standby time 290 ms
Control output (Contact output) SPDT
Switching capacity: 3 A at 250 VAC/30 VDC, resistive load (cos phi=1)
Minimum applicable load: 10 mA at 5 VDC (failure level:P reference value)
Display method 7-segment negative transmissive LCD
Digits 6digits
Character height Measurement value: 10 mm (Red)
Zero suppression: Provided
Comparison value: 6 mm (Green)
Prescaling function Provided (0.001 to 99.999)
Decimal point adjustment Rightmost 3 digits
Key protection Key protect Switch
Teaching function Not provided
Batch counting function Not provided
Communications Not provided
Memory backup EEP-ROM (Number of rewite: 100,000 operations min.Service life: 10 years min.)
Surrounding air temperature Operating: -10 to 55 ℃
Storage: -25 to 70 ℃
Ambient humidity Operating: 25 to 85%
Storage: 25 to 85%
Insulation resistance 100 MΩ min. (at 500 VDC)
Between current carrying terminals and exposed non-current carrying metal parts / Between non-continuous contacts
Dielectric withstand voltage Between current carrying metal parts and non-current carrying metal parts:2000 VAC 50/60 Hz for 1 min
Between power terminals and control input terminals:2000 VAC 50/60 Hz for 1 min
Between control output, and power supply/input circuit:2000 VAC 50/60 Hz for 1 min
Between non-continuous contacts:1000 VAC 50/60 Hz for 1 min
Impulse withstand voltage Between power terminals:3.0 kV
Between current carrying terminals and exposed non-current carrying metal parts:4.5 kV
Noise immunity Between power terminals:±1.5 kV
Between input terminals:±600 V
Square-wave noise by noise simulator (Pulse width: 100 ns/1 µs, 1-ns rise)
Static immunity Mulfunction: 8 kV, Destruction: 15 kV
Vibration resistance (Destruction) 10 to 55 Hz, 0.75-mm single amplitude each in 3 directions for 2 h
Vibration resistance (Malfunction) 10 to 55 Hz, 0.35 mm single amplitude each in 3 directions for 10 min
Shock resistance (Destruction) 300 m/s**2, 3 times each in 6 directions (3 axes)
Shock resistance (Malfunction) 100 m/s**2, 3 times in each directions (3 axes)
Mechanical life expectancy 10,000,000 operations min.
Electrical life expectancy 100,000 operations min. (3 A at 250 VAC, resistive load)
Degree of protection Case front: IEC IP66, UL508 Type 4X (indoors) (when using the Y92S-29 Waterproof Packing)
Mounting method Flush mounting/Surface mounting
External connection method 11-pinSocket
Case color Black (Munsell N1.5)
Weight Approx. 110 g