H5CX-L8D-N

buiding

Type: H5CX-L8D-N


Rated supply voltage 24 VAC 50/60 Hz
12 to 24 VDC 20% max.
Operating voltage range 85% to 110% of rated supply voltage (90% to 110% at 12 to24 VDC)
Power consumption 5.1VA (at 24 VAC)
2.4W (at 24 VDC)
Time ranges(Number of ranges) 10
Time ranges 0.001 s to 9.999 s / 0.01 s to 99.99 s / 0.1 s to 999.9 s / 1 s to 9999 s / 0.1 min to 999.9 min / 1 min to 9999 min / 0.1 h to 999.9 h / 1 h to 9999 h
1sec~99min59sec
Select method Operation Key
Input signals Signal, Reset
Input method No-voltage input
No-voltage input(Solid state input) ON impedance: 1 kΩ max.
Leakage current: Approx. 12 mA
ON residual voltage: 3 V max.
OFF impedance: 100 kΩ min.
(The DC voltage must be 30 VDC max.)
No-voltage input(Contact input) Use contact which can adequately switch 5 mA at 10 V
(The DC voltage must be 30 VDC max.)
No-voltage input(Applicable two-wire sensor) Leakage current: 1.5 mA max.
Switching capacity: 5 mA min.
Residual voltage3.0 VDC max.
Operating voltage: 10 VDC
Output modes A (Signal ON delay1)
A-1 (Signal ON delay2)
A-2 (Power ON delay1)
A-3 (Power ON delay2)
b (Repeat cycle1)
b-1 (Repeat cycle2)
d (Signal OFF delay)
E (Interval)
F (Cumulative)
Z (ON/OFF-duty adjustable flicker)
S (Stopwatch)
toff (Flicker OFF start1)
ton (Flicker ON start1)
toff-1 (Flicker OFF start2)
ton-1 (Flicker ON start2)
Control output (Contact output) Type: SPDT
Switching capacities (Resistive load): 5 A at 250 VAC/30 VDC
Minimum applicable load: 10 mA at 5 VDC (failure level: P Reference value)
One-shot output time 0.01 to 99.99 s
Reset system Power reset (depending on output mode) / Automatic reset (depending on output mode) / External reset / Manual reset
Power reset Minimum power-opening time: 0.5 s (except for A-3, b-1, F, ton-1 and toff-1 mode)
Timer mode Elapsed time (UP) and remaining time (DOWN) (selectable)
Display method 7-segment negative transmissive LCD
Digit 4 digit
Character height Present value: 12 mm (Red)
Set value: 6 mm (Green)
Key protect method Key protect Switch
Memory backup method EEP-ROM
Number of rewite: 100,000 operations min. / Service life: 10 years min.
Ambient temperature Operating: -10 to 55 ℃ When mount timer side by side: -10 to 50 ℃
Storag: -25 to 70 ℃
Ambient humidity Operating: 25 to 85%RH
Total accuracy Accuracy of operating time and setting error (including temperature and voltage influences)
Power-ON start: ±0.01% ±50 ms max.
The values are based on the set value.
Accuracy of operating time and setting error (including temperature and voltage influences)
Signal start: ±0.005% ±30 ms max.
The values are based on the set value.
Insulation resistance 100 MΩ min. (at 500 VDC)
Between current carrying terminals and exposed non-current carrying metal parts / Between non-continuous contacts
Dielectric strength Between current carrying metal parts and non-current carrying metal parts: 2000
between control output and power/input circuit: 2000
Between non-continuous contacts: 1000
Impulse withstand voltage Between power terminals: 1.0 kV
Between current carrying terminals and exposed non-current carrying metal parts: 1.5 kV
Noise immunity Between power terminals: ±1.5 kV
Between input terminals: ±600 V
Square-wave noise by noise simulator (Pulse width: 100 ns/1 us, Rise: 1-ns)
Static immunity Mulfunction: 8 kV, Destruction: 15 kV
Vibration resistance (Destruction) 10 to 55 Hz, 0.75-mm single amplitude each in 3 directions for 2 h
Vibration resistance (Malfunction) 10 to 55 Hz 0.35 mm single amplitude each in 3 directions for 10 min
Shock resistance (Destruction) 300 m/s**2, 3 times each in 3 axes each directions
Shock resistance (Malfunction) 100 m/s**2, 3 times each in 6 directions
Mechanical life 10 million operations min. (under no load at 1,800 operations/h)
Electrical life 100,000 operations min. (5 A at 250 VAC resistive load at 1800 operations/h)
Degree of protection Panel surface: IEC IP66, UL508 Type 4X (indoors) (when using the Y92S-29 Waterproof Packing and Y92F-30 Flush Mounting Adapter)
Mounting method Flush mounting / Surface mounting
External connection method 8-pin round socket
Case color Black (Munsell N1.5)
Accessory (sold separately) Y92A-48F1: Soft Cover
Y92A-48: Hard Cover
Y92F-30: Flush mounting adapter
Y92F-45: Flush mounting adapter
Y92S-29: Waterproof rubber packing
Y92P-CXT4S: Replacement Front Panel
Y92P-CXT4G: Replacement Front Panel
Y92P-CXT4B: Replacement Front Panel
Weight 約115g