UL Type 1/IP 20 drives, 1-phase supply voltage 200…240 VAC, 50/60Hz (3) | ||||||
---|---|---|---|---|---|---|---|
Power | Line Current (2) | Note | Reference (3) | Unit Price | |||
indicated on plate (1) | 200 V | 240 V | |||||
kW | HP | A | A | ||||
0.37 | 0.5 | 6.9 | 5.8 | (4) | ATV71H075M3 | (**) | |
0.75 | 1 | 12.0 | 9.9 | (4) | ATV71HU15M3 | (**) | |
1.5 | 2 | 18.2 | 15.7 | (4) | ATV71HU22M3 | (**) | |
2.2 | 3 | 25.9 | 22.1 | (4) | ATV71HU30M3 | (**) | |
3 | 4 | 25.9 | 22.0 | (4), (5) | ATV71HU40M3 | (**) | |
4 | 5.3 | 34.9 | 29.9 | (4), (5) | ATV71HU55M3 | (**) | |
5.5 | 8 | 47.3 | 40.1 | (4), (5) | ATV71HU75M3 | (**) | |
UL Type 1/IP 20 drives, 1-phase supply voltage 200…240VAC, 50/60Hz | |||||||
Power | Line Current (2) | Note | Reference (3) | Unit Price | |||
indicated on plate (1) | 200 V | 240 V | |||||
kW | HP | A | A | ||||
0.37 | 0.5 | 3.5 | 3.1 | (4) | ATV71H037M3 | ||
0.75 | 1 | 6.1 | 5.3 | (4) | ATV71H075M3 | (**) | |
1.5 | 2 | 11.3 | 9.6 | (4) | ATV71HU15M3 | (**) | |
2.2 | 3 | 15 | 12.8 | (4) | ATV71HU22M3 | (**) | |
3 | 4 | 19.3 | 16.4 | (4) | ATV71HU30M3 | (**) | |
4 | 5 | 25.8 | 22.9 | (4) | ATV71HU40M3 | (**) | |
5.5 | 7.5 | 35 | 30.8 | (4) | ATV71HU55M3 | (**) | |
7.5 | 10 | 45 | 39.4 | (4) | ATV71HU75M3 | (**) | |
11 | 15 | 53.3 | 45.8 | (4), (6) | ATV71HD11M3X | (**) | |
15 | 20 | 71.7 | 61.6 | (4), (6) | ATV71HD15M3X | (**) | |
18.5 | 25 | 77 | 69 | (6) | ATV71HD18M3X | (**) | |
22 | 30 | 88 | 80 | (6) | ATV71HD22M3X | (**) | |
30 | 40 | 124 | 110 | (6) | ATV71HD30M3X | (**) | |
37 | 50 | 141 | 127 | (6) | ATV71HD37M3X | (**) | |
45 | 60 | 167 | 147 | (6) | ATV71HD45M3X | (**) | |
55 | 75 | 200 | 173 | (6) | ATV71HD55M3X | (**) | |
75 | 100 | 271 | 232 | (6) | ATV71HD75M3X | (**) | |
(**) Please contact Schneider Electric distributor for price request (1) These values are for a normal switching frequency of 2.5 or 4kHz, depending on the rating. (2) Typical value for the indicated motor power. (3) To order a special reinforce version for difficult environmental conditions, and S337 at the end of the reference (4) Add the letter "Z" to the end of the reference for an Altivar 71 incorporating a 7-segment terminal (5) A line choke must be used (see accessories for Altivar 71) (6) Drive supplied without EMC filter |
|||||||
![]() |
UL Type 1/IP 20 drives, 3-phase supply voltage 380…480VAC, 50/60Hz | ||||||
---|---|---|---|---|---|---|---|
Power | Line Current (2) | Note | Reference (3) | Unit Price | |||
indicated on plate (1) | 200 V | 240 V | |||||
kW | HP | A | A | ||||
0.75 | 1 | 3.7 | 3 | 3), (4) | ATV71H075N4 | (**) | |
1.5 | 2 | 5.8 | 5.3 | 3), (4) | ATV71HU15N4 | (**) | |
2.2 | 3 | 8.2 | 7.1 | 3), (4) | ATV71HU22N4 | (**) | |
3 | 4 | 10.7 | 9 | 3), (4) | ATV71HU30N4 | (**) | |
4 | 5 | 14.1 | 11.5 | 3), (4) | ATV71HU40N4 | (**) | |
5.5 | 7.5 | 20.3 | 17 | 3), (4) | ATV71HU55N4 | (**) | |
7.5 | 10 | 27 | 22.2 | 3), (4) | ATV71HU75N4 | (**) | |
11 | 15 | 36.6 | 30 | 3), (4) | ATV71HD11N4 | (**) | |
15 | 20 | 48 | 39 | 3), (4) | ATV71HD15N4 | (**) | |
18.5 | 25 | 45.5 | 37.5 | 3), (4) | ATV71HD18N4 | (**) | |
22 | 30 | 50 | 42 | 3), (4) | ATV71HD22N4 | (**) | |
30 | 40 | 66 | 56 | 3), (4) | ATV71HD30N4 | (**) | |
37 | 50 | 84 | 69 | 3), (4) | ATV71HD37N4 | (**) | |
45 | 60 | 104 | 85 | 3), (4) | ATV71HD45N4 | (**) | |
55 | 75 | 120 | 101 | 3), (4) | ATV71HD55N4 | (**) | |
75 | 100 | 167 | 137 | 3), (4) | ATV71HD75N4 | (**) | |
90 | 125 | 166 | 143 | ATV71HD90N4 | (**) | ||
110 | 150 | 202 | 168 | ATV71HC11N4 | (**) | ||
132 | 200 | 239 | 224 | ATV71HC13N4 | (**) | ||
160 | 250 | 289 | 275 | ATV71HC16N4 | (**) | ||
200 | 300 | 357 | 331 | ATV71HC20N4 | (**) | ||
220 | 350 | 396 | 383 | ATV71HC25N4 | (**) | ||
250 | 350 | 444 | 435 | ATV71HC25N4 | (**) | ||
280 | 450 | 494 | 494 | ATV71HC28N4 | (**) | ||
315 | 500 | 555 | 544 | ATV71HC31N4 | (**) | ||
355 | - | 637 | 597 | ATV71HC40N4 | (**) | ||
400 | 600 | 709 | 644 | ATV71HC40N4 | (**) | ||
500 | 700 | 876 | 760 | ATV71HC50N4 | (**) | ||
(**) Please contact Schneider Electric distributor for price request (1) These values are for a normal switching frequency in factory seting mode, depending on the rating. (2) Typical value for the indicated motor power. (3) To order a special reinforce version for difficult environmental conditions, and S337 at the end (4) The letter "Z" to the end of the reference for an Altivar 61 incorporating a 7-segment terminal |