AFPX0L30R | FP-X0

buiding
 

Spec Detail

Item Specifications
Product Number AFPX0L30R
Part Number AFPX0L30R

Performance specifications

Item Specifications
Controllable I/O points : Control unit DC input: 16 points
Relay output: 10 points
Transistor output: 4 points
Controllable I/O points : When using FP-X E16 expansion I/O units -
Controllable I/O points : When using FP-X E30 expansion I/O units -
Controllable I/O points : When using FP0R expansion units -
Programming method/Control method Relay symbol/Cyclic operation
Program memory Built-in Flash-ROM (Free of backup battery)
Program capacity 2.5 k steps
No. of instruction : Basic commands Approx. 114 kinds
No. of instruction : High-level commands Approx. 230 kinds
Processing speed 0.08 μs/step for basic commands, 0.32 μs for high-level commands (MV commands)
Processing speed : Basic time 0.18 ms or less
I/O refreshing + basic time When using E16: 0.4 ms × No. of units
When using E30: 0.5 ms × No. of units
When using FP0 expansion adapters: 1.4 ms + the refreshing time of the FP0 expansion unit
Memory for processing : Relays : External input (X) 960 points
(Note) The actual usable points depend on the combination of the hardware.
Memory for processing : Relays : External output (Y) 960 points
(Note) The actual usable points depend on the combination of the hardware.
Memory for processing : Relays : Internal relay (R) 1,008 points
Memory for processing : Relays : Special internal relay (R) 224 points
Memory for processing : Relays : Timer・Counter (T/C) ・256 points(Note) 
・Timer: (1 ms, 10 ms, 100 ms, 1 s) × 32,767
・Counter: 1 to 32,767
(Note) The points of the timer can be added as required.
Memory for processing : Relays : Link relay (L) No
Memory for processing : Memory area : Data register (DT) 2,500 words
Memory for processing : Memory area : Special data register (DT) 420 words
Memory for processing : Memory area : Link data register (LD) No
Memory for processing : Memory area : File registration (FL) No
Memory for processing : Memory area : Index register (I) 14 words (IO to ID)
Differential points Equivalent to program capacity
Master control relay (MCR) 32 points
Label number (JP+LOOP) 100 points
No. of step programs 128 (Engineering)
No. of subroutines 100
No. of interrupt programs Input: 8 programs
timing: 1 program
Sampling trace No
Comments storage All of the I/O comments,explanations and block comments can be saved. (Free of backup battery, 328 k bytes)
PLC link function No
Constant scan In unit of 0.5 ms: 0.5 ms to 600 ms
Password Available (4 or 8 digits)
Upload protection Available
Self-diagnosis function Checks of the watchdog timer and the program syntax
Program editting during Run Available (Capacity modified simultaneously: 128 steps) But comments cannot be modified during the process.
Downloading during Run Available
High-speed counter : Body input 1-phase, 4-channel (20 kHz max.) and 2-phase, 2-channel (20 kHz max.) 
(Note) The rated voltage is 24 V DC at +25 ℃+77℉. The frequency may fall according to the changes of the voltage, temperature and operating conditions.
(Note) The maximum frequency may vary with the difference of the operating method.
Pulse output/PWM output : Body output Pulse: 2-channel (20 kHz max.) 
or
PWM: 2-channel (1.6 kHz max.) 
(Note) The rated voltage is 24 V DC at 25 ℃. The frequency may fall according to the changes of the voltage, temperature and operating conditions.
(Note) The maximum frequency may vary with the difference of the operating method.
Pulse catch input/Interrupt program 8 points (High-speed counting and interrupt input included)
Periodical interrupt 0.5 ms unit: 0.5 ms to 1.5 sec., 10 ms unit: 10 ms to 30 sec.
Analog input No
Calendar/clock No
Flash ROM backup : Backup made according to commands of F12 and P13 Data memory (2,500 words) 
(Note) The allowable writing operation is within 10,000 times. Areas to be held and not held can be specified using the system registers.
Flash ROM backup : Automatic backup when power OFF Counter: 6 points (C250 to C255) 
Process value of the counter: 6 points (EV250 to EV255) 
Internal relays: 5 points (WR58 to WR62) 
Data memory: 300 words (DT2200 to DT2499) 
(Note) The allowable writing operation is within 10,000 times. Areas to be held and not held can be specified using the system registers.
Backup battery No
RS485 communication port No

General specifications

Item Specifications
CE marking directive compliance Low Voltage Directive,EMC Directive,RoHS Directive
Operating temperature 0 to +55℃ +32 to +131℉
Storage temperature -40 to +70℃−40 to +158℉
Operating humidity 10 to 95% RH (at 25 ℃, no condensation)
Storage humidity 10 to 95% RH (at 25 ℃, no condensation)
Withstand voltage 2,300 V AC, 1 minute
・Input terminals ⇔ Relay output terminals
・All of the transistor output terminals ⇔ All of the relay output terminals
・All of the input terminals⇔ All of the power supply terminals and functional ground terminals
・All of the relay output terminals ⇔ All of the power supply terminals and functional ground terminals
・All of the transistor output terminals ⇔ All of the power supply terminals and functional ground terminals
1,500 V AC, 1 minute
・Power supply terminals ⇔ Ground terminals
500 V AC, 1 minute
・Input terminals ⇔ Transistor output terminals
(Note) The programmable port, RS485 communication port and the internal digital circuit part are non-insulation type.
(Note) The cut-off current is 5 mA (The default value when shipped from the factory) .
Insulation resistance 100 MΩ min. (500 V DC insulation resistance meter) 
・Input terminals ⇔ Output terminals
・All of the transistor output terminals ⇔ All of the relay output terminals
・All of the input terminals ⇔ All of the power supply terminals and functional ground terminals
・All of the output terminals ⇔ All of the power supply terminals and functional ground terminals
・Power supply terminals ⇔ Ground terminals
(Note) The programmable port, RS485 communication port and the internal digital circuit part are non-insulation type.
Vibration resistance 5 to 8.4 Hz, 3.5 mm amplititude in one direction, 1 scan/1 minute 8.4 to 150 Hz,fixed acceleration of 9.8 m/s2, 1 scan/1 minute 10 minutes in X,Y,Z direction each
Shock resistance 147 m/s2, 4 times in X, Y, Z directions each
Noise immunity 1,500 V [p-p] pulse width 50 ns, 1 μs (Measured from nosie simulation method AC power supply termianls)
Operating environment No corrosive gases or too much dust
Conformed EC Directives EMC Directive: EN61131-2
Low Voltage Directive: EN61131-2
Overvoltage class II
Pollution level 2
Weight Net weight:approx. 450g

Power supply specifications(AC power supply)

Item Specifications
Rated voltage 100 to 240 V AC
Applied voltage range 85 to 264 V AC
Inrush current 40A max. (at 240 V AC and 25℃+77℉)
Momentary power off time 10 ms (when 100 V AC used)
Frequency 50/60 Hz (47 to 63 Hz)
Leakage current 0.75 mA max.between the input and protectice ground terminals
Service life of built-in power supply 20000 h (at 55℃+131℉)
Fuse Built-in (replacement disabled)
Insulation system Transformer isolation
Screw of terminal block M3

Power supply specifications(Univeral power supply for intput [output] )

Item Specifications
Rated output voltage 24 V DC
Applied voltage range 21.6 to 26.4 V DC
Rated output current 0.3A
Overcurrent protection Yes
(Note) Output short protection is a temporary overcurrent protection. When the short is detected, all the power supplies of PLC will be turned OFF.
If the current load out of this specifi cation is connected and in consecutive over-loaded status, failures may occur.
Screw of terminal block M3

Input specifications

Item Specifications
Insulation method Optical coupler
Rated input voltage 24 V DC
Applied voltage range 21.6 V DC to 26.4 V DC
Rated input current Approx. 3.5 mA (Control uint: X0 to X3) 
Approx. 4.3 mA (Control unit: X4 and the following ones)
Input points per common 16 points/COM (Input power supply +/- are both available.)
Min. ON voltage/Min. ON current 19.2 V DC/3 mA
Max. OFF voltage/Max. OFF current 2.4 V DC/1.0 mA
Input impedance Approx. 6.8 kΩ (Control units: X0 to X3) 
Approx. 5.6 kΩ (control unit X4 and the following ones)
Response time : OFF→ON For X0 to X3
・common input: 1 ms max.
・When setting high-speed counter, pulse catching input and interrupt input: 25 μs max.(Note) 
X4 and the following ones
・1 ms max.
(Note) The specifications mentioned above are at rated 24 V DC and operationg temperature of 25℃.
Response time : ON→OFF Same as the above.
Action indicator LED indication
EN61131-2 application type TYPE 3 standard (Depending on the above-mentioned specifi cations)

Output specifications(Relay output specifictions)

Item Specifications
Insulation method Relay insulation
Output form 1a output (Relay replacement disabled)
Rated control capacity (Resistance load) 2A 250 V AC, 2A 30 V DC (per point) 
(Note) There are restrictions on the rated current for each output block. Y4 to YD (10 points) Max. 8A in total.
Output points per common 2 points/COM×1, 4 points/COM×2
Response time : OFF→ON Approx. 10 ms
Response time : ON→OFF Approx. 8 ms
Life : Mechanical 20,000,000 times min. (Switching frequency 180 times/minute)
Life : Electrical 100,000 times min. (Depending on the rated control capacity, switching frequency of 20 times/minute)
Surge absorber No
Action indicator LED indication

Output specifications(Transistor (NPN) output specifications)

Item Specifications
Insulation method Optical coupler
Output method Open-collector
Rated load voltage 5 to 24 V DC
Allowable range of load voltage 4.75 to 26.4 V DC
Max. load current 0.5 A
Max. impact current 1.5 A
Output points per common 4 points/COM
Leakage current at OFF status 1 μA max.
Max. voltage drop at ON status 0.3 V DC max.
Response time (at 25℃) : OFF→ON 10 μs max. (Load current over 15 mA)
Response time (at 25℃) : ON→OFF 40 μs max. (Load current over 15 mA)
External power supply (Positive and negative teiminals) Voltage: 21.6 to 26.4 V DC
Current: 15 mA max.
Surge absorber Zener diode
Action indicator LED indication