Item | Specifications |
---|---|
Product Number | CX-411 |
Part Number | CX-411 |
CE marking directive compliance | EMC Directive, RoHS Directive |
Sensing range | 10 m 32.808 ft |
Sensing object | Ø12 mm Ø0.472 in or more opaque object (Note) If slit masks (optional) are fitted, an object of Ø0.5 mm Ø0.020 in (using round slit mask) can be detected. |
Hysteresis | - |
Repeatability(perpendicular to sensing axis) | 0.5 mm 0.020 in or less |
Supply voltage | 12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less |
Current consumption | Emitter: 15 mA or less Receiver: 10 mA or less |
Output | NPN open-collector transistor - Maximum sink current: 100 mA - Applied voltage: 30 V DC or less (between output and 0 V) - Residual voltage: 2 V or less (at 100 mA sink current), 1 V or less (at 16 mA sink current) |
Output:Output operation | Switchable either Light-ON or Dark-ON |
Output:Short-circuit protection | Incorporated |
Response time | 1 ms or less |
Operation indicator | Orange LED(lights up when the output is ON) (incorporated on the receiver for thru-beam type) |
Stability indicator | Green LED(lights up under stable light received condition or stable dark condition) (incorporated on the receiver for thru-beam type) |
Power indicator | Green LED(lights up when the power is ON) (incorporated on the emitter) |
Sensitivity adjuster | Continuously variable adjuster(incorporated on the receiver for thru-beam type) |
Automatic interference prevention function | Two units of sensors can be mounted close together with interference prevention filters. (Sensing range: 5 m 16.404 ft) |
Protection | IP67 (IEC) |
Ambient temperature | - 25 to +55℃ -13 to +131℃ ℉ (No dew condensation or icing allowed ), Storage: -30 to +70℃ -22 to +158℃ ℉ |
Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH |
Ambient illuminance | Incandescent light: 3,000 lx or less at the light-receiving face |
Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure |
Insulation resistance | 20 MOhm , or more, with 250 V DC megger between all supply terminals connected together and enclosure |
Vibration resistance | 10 to 500 Hz frequency, 1.5 mm 0.059 in amplitude (10 G max.) in X, Y and Z directions for two hours each |
Shock resistance | 500 m/s2acceleration (50 G approx.) in X, Y and Z directions three times each |
Emitting element (modulated) | Red LED |
Emitting element (modulated):Peak emission wavelength | 680 nm 0.027 mil |
Material | Enclosure: PBT (polybutylene terephthalate) Lens: acrylic Indicator cover: acrylic |
Cable | 0.2 mm23-core (emitter: 2-core) cabtyre cable, 2 m 6.562 ft long |
Cable extension | Extension up to total 100 m 328.084 ft is possible with 0.3 mm2, or more, cable (both emitter and receiver). |
Weight | Net weight: 95 g approx. Gross weight: 100 g approx. |
Accessory | - |