Item | Specifications |
---|---|
Product Number | GXL-15FU-C5 |
Part Number | GXL-15FU-C5 |
CE marking directive compliance | EMC Directive, RoHS Directive |
Max. operation distance | 5 mm 0.197 in plus or minus 10% (Note) The maximum operation distance stands for the maximum distance for which the sensor can detect the standard sensing object. |
Stable sensing range | 0 to 4 mm 0 to 0.157 in (Note) The stable sensing range stands for the sensing range for which the sensor can stably detect the standard sensing object even if there is an ambient temperature drift and/or supply voltage fluctuation. |
Standard sensing object | Iron sheet 20 × 20 × t 1 mm 0.787 × 0.787 × t 0.039 in |
Hysteresis | 20 % or less of operation distance(with standard sensing object) |
Repeatability | Along sensing axis, perpendicular to sensing axis: 0.04 mm 0.002 in or less |
Supply voltage | 12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less |
Current consumption | 0.8 mA or less (Note) It is the leakage current when the output is in the OFF state. |
Output | Non-contact DC 2-wire type - Load current: 3 to 100 mA (Note 1) - Residual voltage: 3 V or less (Note 2) (Note 1) The maximum load current varies with the ambient temperature. (Note 2) When the cable is extended, the residual voltage becomes larger according to the resistance of the cable. The residual voltage of 5 m 16.404 ft cable length type increases by +0.1 V. |
Output:Utilization category | DC-12 or DC-13 |
Output:Short-circuit protection | Incorporated |
Max. response frequency | 1 kHz |
2-color indicator | Lights up in green under stable sensing condition Lights up in red under unstable sensing condition |
Environmental resistance:Pollution degree | 3 (Industrial environment) |
Protection | IP67 (IEC), IP67 g (JEM) (Note:If using the sensor in an environment where cutting oil droplets splatter, the sensor may be deteriorated due to added substances in the oil. Please check the resistivity of the sensor against the cutting oil you are using beforehand.) |
Ambient temperature | -25 to +70 ℃ -13 to +158 ℉ , Storage: -30 to +80 ℃ -22 to +176 ℉ |
Ambient humidity | 45 to 85 % RH, Storage: 35 to 95 % RH |
Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure |
Insulation resistance | 50 MΩ , or more, with 250 V DC megger between all supply terminals connected together and enclosure |
Vibration resistance | 10 to 55 Hz frequency, 1.5 mm 0.059 in double amplitude in X, Y and Z directions for two hours each |
Shock resistance | 1,000 m/s2 acceleration (100 G approx.) in X, Y and Z directions three times each |
Sensing range variation:Temperature characteristics | Over ambient temperature range -25 to +70 ℃ -13 to +158 ℉ : Within+15-10 % of sensing range at +20 ℃ +68 ℉ |
Sensing range variation:Voltage characteristics | Within plus or minus 2 % for plus or minus 10 % fluctuation of the supply voltage |
Material | Enclosure: PBT Indicator part: Polyarylate |
Net weight | Net weight: 20 g approx. |
Accessories | - |